Tested to BS EN 12825:2001, CISCA 2007 and other widely used standards – both concentrated load and ultimate load performance of HUIYA calcium sulphate anti-static raised access floors meet the requirements of the corresponding load classes.
HUIYA recently completed load performance verification of its CSL 1000–1500 series high-density calcium sulphate anti-static raised access floor at the company’s own laboratory. The programme used GB/T 36340-2018 General specification for raised access floor for electrostatic protection as its base method, and was organised simultaneously around the concentrated load and ultimate load procedures of CISCA 2007 Recommended Test Procedures for Access Floors and BS EN 12825:2001 Raised access floors, which are widely applied in Europe and North America. Results were also compared against other regional systems, including the UK PSA MOB PF2 PS/SPU, KS F 4760 and JIS A 1450:2005. The results show that the product meets the requirements of the corresponding load classes under each standard regime.
1. From multi-standard test methods to a calcium sulphate core product
Raised access flooring is a highly internationalised product. European public projects generally use EN 12825 as the basis for load classification, and it is also referenced by data-centre facility standards such as EN 50600-2-1 and ISO/IEC TS 22237-2. North American tender specifications mostly define design load and ultimate load through the CISCA test procedures. Projects in China follow GB/T 36340 as the main acceptance route. Because “compliant” does not mean the same thing under each regime, HUIYA has long organised finished-product sampling inspections against several standards rather than making a single-basis judgement.
This programme is another practical application of that multi-standard quality system to a calcium sulphate core product. Two key preparatory steps preceded it:
- A visit to the SGS third-party testing institute in Changzhou to study the CISCA 2007 and EN 12825 procedures systematically — concentrated load, deflection, permanent set and ultimate load — including on-site observation of test rigs, loading sequences, environmental parameters and raw-record management (see: HUIYA Visits SGS to Study CISCA 2007 and EN 12825 Raised Access Floor Testing Methods);
- An in-house ultimate load test on a 1500 LBS all-steel raised access floor to CISCA 2007 Section 2, compared against the EN 12825 safety-factor requirements, producing traceable force–displacement curves and peak records (see: HUIYA 1500 LBS All-Steel Raised Access Floor Failure Test | CISCA 2007 and EN 12825 Ultimate Load Verification).
The CSL series verification therefore extends this work from “ultimate-capacity verification of an all-steel product” to “combined serviceability and safety-margin verification of a calcium sulphate core product”. The process is concerned not only with whether the machine can apply load, but also with how specimens are installed, how loading positions are confirmed, how data are recorded, and how results are expressed under different test bases.
2. Why Focus on Concentrated/Ultimate Load Testing
In cloud data centres, equipment rooms and telecom hubs, a floor does not carry the “so many kilonewtons per square metre” quoted on a sample sheet. It carries the four feet of a cabinet, an equipment base or a handling caster – contact areas of only a few square centimetres. However high the uniformly distributed load rating, it will not stop a single cabinet foot from pressing a permanent dent into the panel surface.
High-density calcium sulphate substrate is widely used in such locations precisely because it is dimensionally stable, flat, inherently non-combustible and consistent in electrostatic dissipation. But an inorganic brittle substrate does not usually fail by slowly sagging: it tends to crack suddenly or crush in the core once a critical load is reached. The two indicators must therefore be considered together:
- Concentrated load (point load) is a non-destructive serviceability check – how much the panel deflects under the rated point load, and whether it recovers after unloading;
- Ultimate load is a destructive test – the peak load at the instant the panel fails, used to quantify the safety margin above the working load.
3. Tested Product and Equipment: CSL 1000–1500 Calcium Sulphate Panels + HUIYA’s In-house Load Test Machine
Test samples:
- Product type: high-density calcium sulphate anti-static raised access floor (Calcium Sulphate Raised Access Floor)
- Size: 600 × 600 × 32 mm; dimensional tolerance ± 0.25 mm, flatness ± 0.5 mm (diagonal measurement)
- Core and construction: high-density calcium sulphate substrate, 1600 kg/m³; galvanized steel bottom plate with anti-rust treatment; HPL / ESD conductive PVC / rubber facing; conductive edge banding on all four sides
- Surface resistance: 10⁶ – 10⁹ Ω
- Nominal concentrated load: 4.5 / 5.78 / 6.7 kN (CSL1000 / CSL1250 / CSL1500), corresponding in magnitude to the Chinese B (standard), Z (heavy) and CZ (extra heavy) classes
- Nominal uniform load: 18.0 / 23.12 / 26.8 kN/m²
- Support: adjustable four-point support rig, with all four supports loaded simultaneously and the panel levelled to reproduce installed conditions
These are published product specification ratings, not point-by-point readings from this programme.

Core test equipment:
- Gantry-type (twin-column) servo compression testing machine with a high-precision load cell
- 25.4 mm × 25.4 mm square steel indentor (Rockwell HRC 39–43), flat-faced and aligned perpendicular to the panel. This is the same test geometry as the 1 in² CISCA indentor and the 25 mm EN 12825 indentor
- A 0.01 mm digital dial gauge arranged on the loading axis beneath the panel, for deflection and permanent-set measurement
- Control software continuously acquiring the load–displacement (P–S) curve, allowing the loading, holding, unloading and failure sequence to be replayed
It is worth noting that an approximately 25 mm square indentor, four-point/four-corner support and a load–displacement curve form the common underlying test geometry of the Chinese standard, EN 12825 and CISCA. The differences lie mainly in loading-position layout, load control mode, hold time and acceptance thresholds. One rig can therefore serve several standards — but the data must be recorded and judged separately under each method, and must never be interchanged.
4. On-Site Real Shot: From Batch Samples to the Load–Displacement Curve
The on-site programme set out to confirm two things at once: first, whether deflection at the rated point load and permanent set after unloading satisfy the serviceability requirements; second, whether the peak load before structural failure provides an adequate safety margin above the working load.
Definitions under CISCA 2007:
Concentrated load checks deflection at the rated point load and permanent set after unloading — a non-destructive serviceability check. Ultimate load is the maximum force peak appearing on the force–displacement curve under a constant loading rate — a destructive test. The two serve different purposes and are judged on different bases.
The whole operation was therefore designed around recording deformation and peak force accurately, repeatably and traceably, following: sample pre-check → ID registration → support platform setup → indentor alignment and deflection measurement layout → load parameter setting and curve acquisition → concentrated load / hold / unload → continued loading of a fresh sample to failure → data and image archiving.
Step 1 | Batch sampling and ID registration
Samples were taken from finished panels of a single production batch, prepared together with their matching support components, hand-marked on the face with an ID, logged, and conditioned in the laboratory under the specified environmental conditions. Because ultimate load testing is destructive, every loading position and every failure requires a separate, undamaged specimen — hence the number of spare panels laid out on site at one time. The overturned panel in the photograph shows the dense high-density calcium sulphate core cross-section.

Step 2 | Four-point support platform setup and levelling
The panel is raised on an adjustable four-point support rig and levelled so that all four supports carry load simultaneously and the surface is horizontal, reproducing installed conditions rather than laying the panel flat on a rigid bed. The latter understates deflection and overstates load capacity, and is one of the most common sources of distortion in load testing. Loading positions follow the characteristic points specified by each standard — panel centre, edge midpoint, quarter-diagonal point and corner — with particular attention to the weaker edge zones.

Step 3 | Indentor alignment and deflection measurement layout
The 25.4 mm × 25.4 mm square steel indentor is brought into position perpendicular to the panel, with its geometric centre coincident with the loading point. A 0.01 mm digital dial gauge is placed on the same axis beneath the panel, and indentor travel and deflection readings are fed synchronously into the control software. Because alignment error materially affects point-load readings, this step is re-verified before preload.
Step 4 | Load parameter setting and P–S curve acquisition
Control modes differ between regimes: the Chinese standard and EN 12825 commonly use force control at approximately 120 N/s, whereas CISCA 2007 Section 2 ultimate load testing commonly uses displacement control at approximately 5 mm/min, to avoid falsely high readings caused by impact effects. After the lead tester sets the test mode, loading rate, sampling frequency and peak-lock condition in the control software, the indentor is brought into light contact with the panel (approximately 250 N preload) and the force and displacement readings are zeroed as the measurement datum.

Step 5 | Concentrated load: loading, holding and unloading
Following Clause 7.4.1 of GB/T 36340-2018 and Section 1 of CISCA 2007, the load is increased to the nominal concentrated load for the class and held for 1 min, with deflection at the panel underside recorded; the load is then reduced to 250 N and held for a further 1 min to record permanent set. This stage is non-destructive, so the specimen can be reused for a repeat check at the same loading point.
| Check | What is measured | Requirement (GB/T 36340-2018) | Other regimes |
|---|---|---|---|
| Deflection | Deformation of the panel underside at the rated point load | ≤ 2 mm | EN 12825 deflection classes A / B / C (≤ 2.5 / 3.0 / 4.0 mm); CISCA-based specifications such as VA 09 69 00 use ≤ 0.080 in (2.03 mm) |
| Permanent set | Residual deformation after unloading | ≤ 0.25 mm | Typical CISCA-based limit ≤ 0.010 in (0.25 mm) |
Step 6 | Ultimate load: continued loading of a fresh sample to failure
A separate undamaged sample is loaded by the same method but without stopping at the rated value. Loading continues at a uniform rate until the facing buckles or cracks, the core crushes, the facing debonds or a support becomes unstable and the P–S curve turns over and falls. The peak at the instant of failure is the ultimate load. Curve inflection, peak value and failure morphology are recorded and photographed as evidence. All specimens are destroyed, cannot be recovered, and must never be shared with the concentrated load test.
5. Test Results: Compliance with the Applicable Load Classes
The programme was recorded and assessed separately under Clauses 7.4.1 / 7.4.4 of GB/T 36340-2018, Sections 1 / 2 of CISCA 2007 and the corresponding procedures of EN 12825:2001. The panels met the requirements of the corresponding load classes in both the serviceability and safety-margin checks:
| Metric | What is verified | Acceptance basis | Outcome |
|---|---|---|---|
| Concentrated load | Deflection at the rated point load; permanent set after unloading | Deflection and permanent-set limits set by each regime (GB/T 36340 ≤ 2 mm / ≤ 0.25 mm; EN deflection classes A / B / C; CISCA-based specifications 2.03 mm / 0.25 mm) | Compliant |
| Ultimate load / safety factor | Peak load at structural failure and its ratio to the working load | Chinese standard 3×; EN 12825 safety factor 2 or 3 (working load = ultimate ÷ safety factor); CISCA typically ≥ 2×, government specifications ≥ 2.5× | Compliant |
For reference, the published nominal concentrated load ratings of the CSL series are 4.5 kN (CSL1000), 5.78 kN (CSL1250) and 6.7 kN (CSL1500), corresponding in magnitude to the B (standard), Z (heavy) and CZ (extra heavy) classes of the Chinese standard. These are product specification ratings, not point-by-point readings from this programme; under EN 12825 / CISCA they must be restated using the respective safety factors and classification codes and cannot be treated as directly equivalent to the Chinese classes. Raw readings for every loading position, P–S curves and failure-morphology photographs are retained by the company laboratory, filed separately by standard regime and traceable on request; this release does not disclose specific measured values.
The same panel yields different “rated” values under different standards. The Chinese standard fixes the ultimate at 3 × the rated load; EN 12825 first measures the ultimate and then divides by 2 or 3 to obtain the working load, and is meaningful only when written as a four-part code together with the deflection class and dimensional-tolerance class; North American CISCA centres on the design load (including yield-point control). Any load figure quoted in a specification or test report should therefore state the standard, edition, safety factor and loading position at the same time — a bare kN value cannot be compared across markets.
6. About the HUIYA CSL 1000–1500 / Calcium Sulphate Anti-static Raised Access Floor
The CSL series serves cloud data centres, equipment rooms, telecom equipment rooms, cleanrooms and similar environments with demanding requirements for both electrostatic control and load-bearing capacity.
| Item | Specification |
|---|---|
| Panel size / thickness | 600 × 600 mm / 32 mm |
| Core | High-density calcium sulphate substrate, 1600 kg/m³ |
| Bottom protection | Galvanized steel sheet + anti-rust coating |
| Surface finish options | HPL, ESD conductive PVC, rubber |
| Surface resistance | 10⁶ – 10⁹ Ω |
| Dimensional tolerance | ± 0.25 mm; flatness ± 0.5 mm (diagonal measurement) |
| Support system | Steel pedestals + stringers + screw fixing, adjustable height 55 – 2000 mm |
| Nominal concentrated load | 4.5 / 5.78 / 6.7 kN (CSL1000 / CSL1250 / CSL1500) |
| Nominal uniform load | 18.0 / 23.12 / 26.8 kN/m² |
7. Making Load Testing of Raised Access Floors Routine Before Shipment
For HUIYA, the combined concentrated and ultimate load verification of the CSL 1000–1500 calcium sulphate floor carries three layers of significance:
- Method: the CISCA 2007 / EN 12825 operating details learned earlier at SGS and the established Chinese method were executed as separate regimes on the same test rig, confirming that the in-house laboratory can handle the combined “serviceability + safety margin” indicators;
- Product: the CSL series serves cloud data centres, financial computer rooms, telecom equipment rooms and cleanrooms, where cabinet feet, equipment bases and handling casters create point loads rather than uniform loads. Only when concentrated load and ultimate load both qualify is structural redundancy left for long-term operation;
- System: multi-standard sampling inspection is extended from all-steel products to calcium sulphate core products, with photographs, video, curves and raw readings forming a reviewable record chain, bringing a near-third-party perspective into routine pre-shipment checks.
HUIYA has long carried out pre-delivery sampling inspections of finished products against multiple regimes — GB/T 36340-2018 (China), CISCA 2007 (USA), BS EN 12825:2001 (Europe), KS F 4760 (Korea) and JIS A 1450:2005 (Japan). This programme is another working record of that multi-standard quality system in day-to-day operation.
A raised access floor is not merely a finishing material; it is the “second ground” that carries precision equipment and critical operations. HUIYA will continue to use international standards as its methodological baseline and reliable quality data as a common language, working with customers, design institutes, general contractors and third-party testing bodies to move the Chinese raised access floor industry towards greater standardisation and traceability.
About HUIYA — Changzhou Huiya Decorative Materials Co., Ltd. specialises in raised access floor system manufacturing, supplying products and solutions for data centres, cleanrooms and commercial office projects.
Huiya Real-Time News
Huiya Real-Time News is dedicated to providing you with the latest and most authoritative information on the raised flooring industry.
We provide 24/7 updates on industry policy interpretations, market trend analysis, company news.
Liquid Cooling Data Center Flooring Solutions
MORE DOWNLOADS
GENERAL CATALOGUE
HUIYA INTRODUCTION
HUIYA GREEN LABEL

CAD/BIM FULL STEEL
APPLICATION SCENARIOS